Leak Rate Testing

Base Testing of Apparatus

          In order for accurate leak detection the testing apparatus must have a leak rate less than that of the maximum leak rates of the lids.   To make sure the apparatus met this requirement, the team preformed a pressurized bubble test on the welds and fittings of the apparatus.    The team’s pressurized leak rate testing procedure is covered in its own section below.   Figure 1 shows the team’s pressurized bubble test of the testing apparatus’ welds to determine if the testing apparatus was sound enough to hold a vacuum.   The team found two pinhole size cracks in the top and bottom welds where air was able to flow freely.   The problem was solved by placing RTV® silicone along the interior weld surfaces of the test apparatus, and pressurizing the apparatus to force the RTV® into the voids, solving the problem of leaking welds.  

 

Figure 1: Bubble test of testing apparatus welds

 

          The valve and fitting assemblies were also tested to ensure leak rates less than 10^-3 Std cc/s but were tested using a pressure gradient leak test.   Figure 2 shows the testing procedure, where the pressure transducer was connected directly to the venturi/valve assembly using a 1/8 inch NPT coupler.   The testing pressure gradient testing procedure is discussed in the Pressure Gradient Leak Testing section.   Using this method, the team found the combined leak rate of the assembly to be 10^-7 Std cc/s, well below the 10^-3 Std cc/s required for the lids.

 

Figure 2: Pressure gradient testing of valve

 

Plan for Testing

          Once the leak testing apparatus was determined to leak less than 10^-3 Std cc/s, the team was ready to begin testing of their lid/sealing system designs.   Lid/sealing systems designed by the team are run through three tests (1) pressurized bubble test, (2) Magnaflux Spotcheck® dye penetration test, (3) pressure gradient leak test.   Each giving the team increased leak rate detection sensitivity.  

 

Pressurized Bubble Test:

          Team Leaks for Weeks tested each lid/sealing system first using the pressurized bubble test.   The pressurized bubble tests can produce evidence of leak rates down to 10^-4 Std cc/s, and is relatively easy to perform by simply creating a pressure gradient between two volumes, and spraying soapy water on the surface with lower pressure.   Figure 2 shows bubble testing on the first attempt at using an O-ring.

 

Figure 3: Bubble testing of aluminum contoured lid

Click here to see pressurized bubble test video.

Magnaflux® Dye Penetration Test:

          If the lid/sealing system passed the pressurized bubble test, the next step was to perform a dye penetrant test.   The team used Magnaflux Spotcheck® as our dye penetrant.   Dye penetrates are capable of showing evidence of leak rates to determine if the leak rate was greater than 10^-5 Std cc/s.   The team preformed the dye penetrant test by using the venturi to pull a vacuum within the apparatus, then spraying the red dye penetrant on the outside surface of the seal area.   After waiting the recommended 30 minute penetration time, the team opened the valve, pressurizing the apparatus, and removed the lid for inspection.   The team then sprayed a developer on the inner seal surface to enhance ability for visual inspection.  

 

Figure 4: Magnaflux test of aluminum contoured lid

Pressure Gradient Leak Testing:

          Although the pressurized bubble and the dye penetrant tests allowed the team quick visual inspection of sealing capability, a quantitative test was required.   The team chose to use a pressure gradient leak test to quantify and standardize each lids leak rate.   Two pressure transducers were used to measure the apparatus’ internal pressure and the atmospheric pressure.   The voltage across the two transducers was measured using two 5-digit multimeters that were connected to our test computer using a GPIB connection.   The team created a LabVeiw® program to collect the voltage measurements taken by the two digital multimeters.   The team then analyzed the data using Microsoft Excel®.   The leak rate was calculated using the following equation derived by the team:

                    Where

                                                L =    Leak Rate (Std cc/s)

                                                P1=    Initial Internal Pressure (psia)

                                                P2=    Final Internal Pressure     (psia)

                                                V=     Apparatus Internal Volume (cm^3)

                                                t=      Time Between Readings (s)

 

 

Figure 5: Pressure Gradient Leak Test Apparatus

 

Figure 5: Leak Testing Computer, DMM, Power Supply

 

 

 

1. Nondestructive Testing Handbook: Volume 1, Leak Testing; Third Edition; 1998, American Society for Nondestructive Testing; Table 4, page 20